Question Details

A 3-phase,  11 kV , 10 MVA  synchronous generator is connected to an inductive load of power factor  ( 3 / 2 )  via a lossless line with a per-phase inductive reactance of 5Ω. The per-phase synchronous reactance of the generator is 30Ω with negligible armature resistance. If the generator is producing the rated current at the rated voltage, then the power factor at the terminal of the generator is

Options

A

0.63 lagging

B

0.87 lagging

C

0.63 leading

D

0.87 leading

Show Answer

Correct Answer :

Option A

0.63 lagging

Solution :

The correct answer is 0.63 lagging.

To find the power factor at the terminal of the generator, we need to analyze the phasor relations of the system on a per-phase basis.

Step 1: Calculate the rated terminal voltage (per-phase) and rated current of the generator
The generator is operating at rated conditions, so the line-to-line terminal voltage is:
VL-L = 11 kV
The rated per-phase terminal voltage of the generator is:
V t = 11000 3 6350.85  V

The rated apparent power of the 3-phase generator is S = 10 MVA. The rated current (which is also the line current and the phase current in a star-connected system) is:
I = S 3 × V L-L = 10 × 10 6 3 × 11000 524.86  A

Step 2: Express the current and line voltage drop using the load voltage as reference
Let the load phase voltage VL be the reference phasor:
VL = VL ∠ 0° V
Since the load is inductive and has a power factor of cos(φL) = 3/2 lagging, the phase angle of the load is:
φL = arccos(0.866) = 30°
So, the load current lags the load voltage by 30°:
I = I ∠ -30° A = 524.86 ∠ -30° A

The generator is connected to the load through a transmission line with a per-phase inductive reactance of Xline = 5 Ω.
The generator terminal voltage (per-phase) is related to the load voltage by:
Vt = VL + j I Xline

First, calculate the voltage drop across the line reactance:
j I Xline = (1 ∠ 90°) × (524.86 ∠ -30°) × 5
j I Xline = 2624.3 ∠ 60° V
j I Xline = 2624.3 × (cos 60° + j sin 60°) V
j I Xline = 2624.3 × (0.5 + j 0.866) = 1312.15 + j 2272.71 V

Thus, the terminal voltage phasor is:
Vt = (VL + 1312.15) + j 2272.71 V

Step 3: Solve for the load voltage magnitude VL
Since the magnitude of the generator terminal voltage is rated at |Vt| = 6350.85 V, we can write:
| V t | 2 = ( V L + 1312.15 ) 2 + ( 2272.71 ) 2
( 6350.85 ) 2 = ( V L + 1312.15 ) 2 + 5165211
40333296 = ( V L + 1312.15 ) 2 + 5165211
( V L + 1312.15 ) 2 = 35168085
VL + 1312.15 = 5930.27 V
VL = 4618.12 V

Step 4: Find the power factor at the terminal of the generator
Substitute VL back into the expression for Vt:
Vt = (4618.12 + 1312.15) + j 2272.71 = 5930.27 + j 2272.71 V

The angle θt of the terminal voltage phasor with respect to the load voltage reference is:
θ t = arctan ( 2272.71 5930.27 ) = arctan ( 0.3832 ) 20.97 °

The current phasor has an angle of θi = -30°.
The phase difference φ between the generator terminal voltage and the current is:
φ = θt - θi = 20.97° - (-30°) = 50.97°

Thus, the power factor at the terminals of the generator is:
cos(φ) = cos(50.97°) ≈ 0.63
Since the current lags the terminal voltage (θi < θt), the power factor is 0.63 lagging.

Unlock Our Free Library

Access expert-curated educational resources and study materials—completely free.

Discover more resources

You may also like

Ask AI Tutor
5 left
Q1 View Question & Options
AI Tutor is solving this question...
Reading question context & options...