Two generating units rated for 250 MW and 400 MW have governor speed regulations of 6% and 6.4%, respectively, from no load to full load. Both the generating units are operating in parallel to share a load of 500 MW. Assuming free governor action, the load shared in MW, by the 250 MW generating unit is ______. (round off to nearest integer)
Correct Answer :
Solution :
The correct answer is 200.
Step-by-step Explanation:
Let us define the parameters for the two generating units operating in parallel:
For Unit 1 (250 MW unit):
Rated capacity:
Governor speed regulation:
For Unit 2 (400 MW unit):
Rated capacity:
Governor speed regulation:
Let the load shared by Unit 1 be (in MW) and the load shared by Unit 2 be (in MW).
The total load shared by both units is 500 MW:
Assuming free governor action, both units operate at the same system frequency. Therefore, the change in frequency (or percentage drop in speed/frequency from no load to the operating load) must be identical for both generators:
Substituting the given values into the equation:
Simplifying the relation:
Now, substitute this relationship into the total load equation:
Thus, the load shared by the 250 MW generating unit is 200 MW.